Current Transducer857-550857-552

The 857-550 Current Transducer detects alternating and direct currents from 0 – 1 A and 0 – 5 A, and converts the input signal into an analog standard signal at the output (e.g., 4 – 20 mA).

The 857-552 Rogowski transducer records RMS values from alternating currents via a Rogowski coil and converts the input signal into a standard analog signal on the output side (e.g. 4 – 20 mA).
Input signal
AC/DC 0 – 1 A
AC/DC 0 – 5 A

Rogowski coils
500 A/2000 A
Frequency range16 Hz – 400 Hz16 Hz – 1000 Hz
Output signalVoltage: 0 – 5 V, 1 – 5 V, 0 – 10 V, 2 – 10 V
Current: 0 – 10 mA, 2 – 10 mA, 0 – 20 mA, 4 – 20 mA
Digital output DODC 24 V/100 mA
DC 24 V/100 mACurrent ≤ 600 Ω, Voltage ≥ 2000 ΩCurrent ≤ 600 Ω, Voltage ≥ 1000 Ω
Supply voltageVDC 24
Current Transducer2857-550
WAGO's 2857-0550 Current Transducer is used for measuring, isolating and converting AC/DC currents into standard signals in various industries, such as processing, sewage, power technology or machinery, and plant engineering. Transducers protect installations, systems and persons via electrical isolation of measurement signals (immunity to external interferences, such as differential signals or floating grounds, rise in potential) or via overcurrent monitoring. WAGO's transducer is ideal for current measurement and overcurrent detection, while simultaneously isolating field signals to the central control system for further signal processing. Measured values can be optimally displayed and settings can be changed using WAGO's 2857-0900 Display.
Input signalAC/DC 100 A
Frequency range15 – 2000 Hz
Output signalCurrent: ± 10 mA; 0 – 10 mA; 2 – 10 mA;
± 20 mA; 0 – 20 mA; 4 – 20 mA
Voltage: ± 5 V; 0 – 5 V; 1 – 5 V;
± 10 V; 0 – 10 V; 2 – 10 V
Output – Digital24 VDC/100 mA
Output – Relay1 changeover (1U)
250 VDC/6 A
ResistanceCurrent < 600 Ω
Voltage > 1000 Ω
Nominal supply voltage24 VDC

Connection examples

You can find connection examples here. continue...

Configuration and Visualization

The interface-configuration software – DIP Switch Alternative, and the JUMPFLEX®-ToGo configuration app – DIP Switch Alternative. continue...

Back to the Overview

  • Newsletter Subscription
  • How may we help?
  • Add to bookmark list
en
The document could not be added to the bookmark list.
Item was added to the bookmark list successfully.
Page was added to the bookmark list successfully.
Digital Media was added to the bookmark list successfully.
Document was added to the bookmark list successfully.
../../../../navigation-complete.html